- The Periodicity trial operation is necessary for standby generator sets.
- Firstly finish all the inspection work before starting.
- Connect the battery to the genset, first with positive pole, then with negative pole
- Start diesel genset from the controller
- Check the abnormal noise or vibration of the genset
- Check if there is leakage problem for the three liquids (coolant, fuel and oil) & air exhaust system have leakage phenomenon.
- Check if there is any unusual indication on the meter of control system.
- Check the output voltage and frequency from the control screen
- Every starting, stopping or one hour running, record the operating parameter of the genset one time.
- Keep the load of genset without exceeding rated value.
- Check whether the gensets can start automatically after get a signal from ATS.
- Start the synchronization function once the gensets are working smoothly.